Tulkot latviski
PowerWalker VFI 3000 RMG PF1 Double-conversion (Online) 3 kVA 3000 W
PowerWalker VFI 3000 RMG PF1 Double-conversion (Online) 3 kVA 3000 W
Code: EB403531839
Manufacturer's product code: VFI 3000 RMG PF1
Manufacturer's product code:
VFI 3000 RMG PF1
Manufacturer, Brand: POWER WALKER
Manufacturer, Brand:
POWER WALKER
1 324,46 €
incl. VAT / gb
At supplier's warehouse 1
⛟ Delivery 3-5 working days after payment.
⛟ Delivery 3-5 working days after payment.
Input operation voltage (min) | 110 V |
Input current Total Harmonic Distortion (THD) | 1.6% |
Input frequency | 40/70 Hz |
Input operation voltage (max) | 300 V |
Noise level | 50 dB |
Surge protection | Yes |
Surge protection features | Modem, Fax, Network |
Output operation voltage (max) | 240 V |
Output operation voltage (min) | 200 V |
UPS topology | Double-conversion (Online) |
Emergency Power Off (EPO) | Yes |
Output power capacity | 3 kVA |
Output voltage regulation | 1% |
Output voltage Total Harmonic Distortion (THD) | 2% |
Power factor | 0.99 |
Output power | 3000 W |
Waveform | Sine |
Crest factor | 3:1 |
Display type | LCD |
Product colour | Black |
Form factor | Rackmount/Tower |
Operating relative humidity (H-H) | 20 - 95% |
Operating temperature (T-T) | 0 - 40 °C |
Width | 190 mm |
Weight | 27.5 kg |
Height | 318 mm |
Depth | 630 mm |
Resource CD | Yes |
Warranty card | Yes |
Package width | 600 mm |
Package type | Box |
Package height | 200 mm |
Manual | Yes |
Cables included | Input power cable, Output power cable, USB cable |
Emergency Power Off (EPO) connector | Yes |
USB 2.0 ports quantity | 1 |
Power plug | C14 coupler |
Modem (RJ-11) ports | 1 |
Serial interface type | RS-232 |
Ethernet LAN (RJ-45) ports | 1 |
Serial interface | Yes |
AC outlet types | C13 coupler, C19 coupler |
RS-232 ports | 1 |
Number of type F outputs | 9 |
USB port | Yes |
Battery voltage | 12 V |
Typical backup time at half load | 10.1 min |
Battery recharge time | 3 h |
Typical backup time at full load | 3 min |
Battery capacity | 9 Ah |
Number of batteries supported | 6 |
Harmonized System (HS) code | 85078000 |
Warnings | Do not disassemble the unit housing, there may be a risk of electric shock. |