Tulkot latviski
Meter: insulation resistance | LCD (9999) 19mm | Bargraph: 29segm.
Meter: insulation resistance | LCD (9999) 19mm | Bargraph: 29segm.
EB Kodas: EB993372576
Gamintojo prekės kodas: UT511
Gamintojo prekės kodas:
UT511
Gamintojas, prekės ženklas: UNI-T
Gamintojas, prekės ženklas:
UNI-T
181,07 €
PVM įskaičiuotas / gb
Tiekėjo sandėlyje >10 vnt
⛟ Pristatymas 1-3 darbo dienos po apmokėjimo.
⛟ Pristatymas 1-3 darbo dienos po apmokėjimo.
Type of meter | insulation resistance |
Kind of display used | LCD |
Display parameters | (9999) |
Measurement | AC voltage |
Measurement | DC voltage |
Measurement | insulation resistance |
Bargraph | 29 segm. |
Insulation resistance measuring accuracy | ±(3% + 5digit) |
AC voltage measuring range | 1...30V |
AC voltage measuring range | 750V |
AC voltage measuring accuracy | ±(2% + 3 digit) |
DC voltage measuring range | 1...30V |
DC voltage measuring range | 600V |
DC voltage measuring accuracy | ±(2% + 5 digit) |
Continuity test | acoustic indication |
Continuity test | <30Ω |
Test voltage | 100V |
Test voltage | 250V |
Test voltage | 500V |
Test voltage | 1kV |
Conform to the norm | CAT II 1000V |
Conform to the norm | CAT III 600V |
Conform to the norm | EN 61010 |
Protection | anti-overload OPP |
Measuring instrument features | 4 methods of insulation resistance measurement: continuous, during determined time, polarization index and comparative measurement |
Measuring instrument features | automatic power-off |
Measuring instrument features | autoranging |
Measuring instrument features | low battery indicator |
Standard equipment | crocodile clips |
Standard equipment | hard case |
Standard equipment | test leads |
Power supply | battery LR14 1,5V x8 |
Pollution degree | 2 |
Weight with battery | 2kg |
Body dimensions | 202x155x94mm |
Insulation resistance measuring ranges | 0.1...100MΩ |
Insulation resistance measuring ranges | 500MΩ |
Insulation resistance measuring ranges | 1GΩ |
Insulation resistance measuring ranges | 2GΩ |
Insulation resistance measuring ranges | 4GΩ |
Insulation resistance measuring ranges | 10GΩ |
Battery/ rechargeable battery | battery LR14 1,5V x8 |
Measurement memory | 18 |
Display height 1 | 19mm |