Tulkot latviski

Ühefaasiline elektriarvesti | Mitmetariifne | MODBUS-protokoll näitude kauglugemiseks

EB Kood: 1F-1DIN 1101 Multi

 26,91  
Sisaldab käibemaksu / gb
0 Laos 
-+

  • Elektriarvesti võimaldab mõõtmist mõlemas suunas: arvestist ja arvestini, mis sobib ideaalselt päikesepaneelisüsteemide jaoks.
  • Arvestusrežiime saab seadistada vastavalt kellaajale, mis on mugav, kui elektritariif muutub olenevalt kellaajast.
  • Arvesti võimaldab kaugedastust MODBUS-protokolli abil.

Products Character:
1.Max 100A Direct Connect
2. Standard 1-modulus width,TH35-7.5 type  rail installation 
3.Touch key design improves the operation of the keys and reduces the key failure rate.
4.Multi-function parameter measurement for voltage, current, active power, reactive power, apparent power, power factor, and phase angle
5.Support di-direction energy measuring, providing monthly electricity consumption statistics for the last 12 months, and daily electricity consumption statistics for the last 31 days
6.Support dual timing of meter start up running time and load running time
7.Support access of two rate switching signals and realize power metering of two rates
8.Support 1 passive pulse output, 1 RS485 communication, Baud rate up to 38400bps, support Modbus RTU, DL/T645-2007 protocol
9.LCD display, white backlight, backlight lighting time is adjustable.
10. LCD refresh time: 1 second, support manual page turning and automatic turning display (can be set to switch)

 

1Measurement parameters for LCD display (while supporting communication reading)
Instantaneous time value (RMS valid value)
Current Phase current
Voltage Phase voltage
Frequency 45 to 65Hz
Power Active power, Reactive power, Apparent power
Power factor Power factorphase angle
Energy Values (include: import, export, import + export)
Active energy 0 to 999999.999 kWh,LCD display digits4+2 -> 5+1 -> 6+0
Reactive energy 0 to 999999.999 kvarh,LCD display digits4+2 -> 5+1 -> 6+0
Multi-Tariff active energy (T1 - T4) Active power of T1, T2, T3 and T4, range: 0 ~ 999999.999 kWh (LCD displays: 4 + 2-> 5 + 1-> 6 + 0)
Maximum Demand Values
Max.Demand of current Phase current
Max.Demand of power Active power, Reactive power, Apparent power
2. only communication read measurement parameters
Energy Values
Electricity of each phase active and reactive power of each phase, including: positive, negative, positive+negative, range: 0 ~ 999999.999 Wh / varh
Multi-Tariff reactive energy  (T1 - T4) Active and reactive power (including positive, negative, positive+ negative) of T1, T2, T3 and T4, range: 0 ~ 9999999.999 Wh / varh
Monthly electricity consumption for the last 12 months Active power, reactive power, respectively include: positive, negative, positive+ negative , range: 0 ~ 999999.999
Daily energy consumption for the last 31 days Active power, respectively include: positive, negative, positive+ negative , range: 0 ~ 999999.999
3. The Unit can settable
Communication class Modbus address, baud rate, parity bit, stop bit
System configuration class User password (HMI)
Demand class Demand interval period, Slide time
Pulse output class Pulse output type, Pulse output width, Pulse output rate
Time class Automatic scroll display time, Backlit time, System time (RTC), Tariff time

 

Electrical Characteristics
Type of measurement effective value measurement (RMS), support single phase two lines.
Measurement accuracy Voltage, Current Class 0.5, according IEC 61557-12
Active power Class 1 / 0.5, according IEC 61557-12
Reactive power Class 2, according IEC 61557-12
Apparent power Class 1, according IEC 61557-12
Active energy Class 1 / 0.5S, according IEC 62053-22, IEC 61557-12
Reactive energy Class 2, according IEC 62053-23,Class 2, IEC 61557-12
Power factor Class 1, according IEC 61557-12
Frequency Class 0.2, according IEC 61557-12
Data update rate 1 second. Optional 100 ms
Input-Voltage Rate voltage 230 Vac / 110 Vac (Option)
(Un)
Direct connection Measured range : 176 to 275 Vac / 85 to 144 Vac (Option)
Frequency range 45 to 65 Hz
Overload capacity 2*Un for 1 second
Input-Current Measured range 0.005 to 100 A, basic current (Ib) is 5A
Overload capacity 2 x rated data for 1 second
Pulse output Output type Optical coupled pulse with an open collector
Pulse constant 1000 / 100 / 10 / 1 imp/kWh(kvarh) (Configurable)
Pulse width 60/100/200 milliseconds (Configurable), default is 100milliseconds
Pulse output type Import/export/total active energy/total reactive energy (Configurable)
Output level Class A, according IEC 62053-31
Input voltage 5 ~ 27 Vdc
Pulse indicator light on the panel Pulse constant is 1000imp/kWh
Real-time clock accuracy 0.5 s/d
Mechanical Characteristics
IP Degree of Protection (IEC 60529) Designed to IP51 front display, IP30 meter body
Dimensions (W X H X D) 20 x 117 x 73 mm
Mounting Position DIN Rail mounting
Fire protection level of the meter shell material UL 94 V-0
Environmental Characteristics
Operating Temperature -25 to +55
Storage Temperature -40 to +80
Humidity < 90%, non-condensing
Pollution Degree 2
above sea level <2000m
Anti-vibration index 10 Hz to 150Hz, IEC 60068-2-6
Electromagnetic Characteristics
Electrostatic Discharge Level 4, according IEC 61000-4-2(1)
Immunity to Radiated Fields Level 3, according IEC 61000-4-3(1)
Immunity to Electrical Fast Transients Level 4, according IEC 61000-4-4(1)
Immunity to Surges Level 4, according IEC 61000-4-5(1)
Immunity to Conducted Disturbances Level 3, according IEC 61000-4-6(1)
Immunity to Magnetic Fields IEC 61000-4-8(1)
Immunity to Voltage Dips IEC 61000-4-11(1)
Radiated Emissions Class B, according EN55011
Conducted Emissions Class B, according EN55011
Harmonics IEC 61000-3-2(1)
(1): The experimental test is carried out according to the grade requirements of industrial grade products in IEC61326-1
Safety
Measurement Category CAT III, according IEC 61010-1
Overvoltage Category CAT III, according IEC 61010-1
Insulation AC Voltage Test: 4kV for 1 minute
Impulse Voltage Test: 6kV - 1.2/50µS waveform
Protective Class double insulation , according IEC61010-1
Communications
Interfaces standard and protocols 2-wire RS485, Modbus RTU(default),DL / T645-2007, MBus (optional)
Baud rate 1200,2400,4800,9600 bps (default), 19,200 bps
Parity bit None, Even, Odd, default is None
Stop bit 1 or 2, default is 1
Response time <100ms
Transmission mode half-duplex
Transmission distance Up to 1000m
Max. Bus loading 64 pcs